Back to Air conditioning

KTRVB-052.244

Room thermostat, heating/cooling, surface-mounted, 24 VAC/VDC, output 0…10 V / 10…0 V, 2-/4-pipe

Electronic surface-mounted air conditioning controller for heating/cooling control in 2- and 4-pipe systems for hotel, residential and commercial premises. Designed to control continuous valve actuators, both normally closed and normally open. Particularly suitable for cooling ceiling control due to the possibility of dew point monitoring. To compensate for the inertia of controlled systems with chilled ceilings, the device has a temperature sensor input for connecting an external radiation sensor (optional). The external sensor can also be designed as a room sensor (optional) as an authority variant, where the controller should be inaccessible to unauthorized persons. An internal potentiometer can be used to select the use of the internal or external sensor or the use of both sensors with an adjustable weighting. Contact inputs for ECO function and OFF (frost protection).


SKU: DA451500 Categories: , ,
Number of outputs2, 2
Number of outputs, heating1
Number of outputs, cooling1
Actual temperature displayNo
Temperature controller versionclimate controller
Output signalcontinuous, 0 … 10 V
External settingYes
Operationrotary knob
Operating voltage24 VAC ±8 %, 50 Hz / 24 VDC ±20 %, 24 VAC, 50 Hz / 24 VDC
DesignBerlin 2000
DisplayNo
ECO input (reduction)24 VAC, 50 Hz / 24 VDC
ECO function (reduction)Yes
Electric connectionscrew terminals
Electronic controlYes
Colourpure white
RAL colour number (similar)9010
Sensor elementNTC internal, optional NTC external
Bearing temperature–20 … 70 °C
Max. air humidity (non-condensing)95 % r.H.
Housing materialplastic ABS
Max. switching current5 mA
Mechanical range reductionYes
MediumAir
With receiverNo
Mounting/attachmentsurface mounting
Neutral zone2 K
Surface finishmatt, matt
Control range13 … 29 °C, 13 … 29 °C
Heating control function
Cooling control function
Control behaviourPI
Switching differentialHeating/cooling: 0 K
Switching difference, can be adjustedNo
Switching elementelectronics with analogue output signal
Switch Off/Comfort/ECONo
On/Off switchNo
Heating/cooling switchNo
Additional heating switchNo
Switch/lamp night-time reductionNo
Switching contactzero-contact
Potential free switching contactNo
Protection classIP30
Protection classIII
Sensor externalNo
Safety and EMCin accordance with DIN EN 60730
ScaleThreshold arrows with ”+” and ”-“
Ambient temperature0 … 40 °C
Type of wiringother
Degree of contamination2
Assemblycomplete device
Dimensions (W x H x D)78,3 mm x 83,4 mm x 25,5 mm

Loading specification text...

PhotoTypeArt. no.Features
TPS 1TPS 1G8000299Dew point sensor for cooling ceilings/mats, 10 m cableView product
TPS 2TPS 2G8000300Dew point sensor for cooling ceilings/pipe, 10 m cableView product
TPS 3TPS 3SN120000Dew point sensor for pipes, 10 m cableView product
ALF-2ALF-2G9050160Contact temperature sensor, NTC 47KView product
AF-2AF-2G9040380Outdoor temperature sensor, NTC 47KView product
KF-2KF-2G9031446Cable temperature sensor, NTC 47K, 1.5 m, sensor cable PE, -35...+100 °CView product
PFC 47/6mPFC 47/6mG9130180Radiation temperature sensor, pendulum, NTC 47K, 6 mView product
BTF2-C47-0000BTF2-C47-0000SA140014Room temperature sensor, NTC 47K, surface-mounted super flatView product
FUFC 47-0000FUFC 47-0000SN090198Room temperature sensor, NTC 47K, flush-mounted, cover 50 x 50 mm, pure white glossyView product
STF-2STF-2SN080200Radiation temperature sensor, 2x NTC 47KView product