Skip to main content

Dew point sensor for cooling ceilings/mats, 10m cable

TPS 1

Dew point sensor for cooling ceilings/mats, 10m cable

This dew point sensor was specially developed in conjunction with an alre dew point monitor (e.g. WFRRN) or chilled ceiling controller (e.g. KTRRB, KTRRU, KTRRUu, KTRVB, KTFRx) to detect and report the dew point. When installed correctly, it prevents condensation dripping from the cooled parts of the cooling circuit. Application: Drywall cooling ceiling (plasterboard) with attached capillary tube mat, metal cooling ceiling with integrated capillary tube system. Installation/fastening is carried out using clips on the cooling ceiling capillary tube. Sensor cable can be extended up to 50 m with 2 x 0.5 mm².
  • Art.-Nr.: G8000299

    Technical data

    Assembly sensor, 2 clips for cooling pad
    Bearing temperature –20 … 70 °C
    Dimensions (W x H x D) 70 mm x 21,5 mm x 36 mm
    Length of supply line 10 m
    Measurement of dew point Yes
    Montage/Befestigung to the cooling ceiling capillary pipe
    Protection class IP30
    Version of sensor humidity sensor
    With explosion protection No
    With mounting material Yes
    With supply line Yes