Back to System technology

JTF-3 W

Frost protection thermostat, capillary length 1.8 m, internal setting

For protecting hot water heating registers against freezing. The device is intrinsically safe and has a sealable setpoint adjustment.

For temperature measurement of non-aggressive gases in the duct, use the SW-200-12 thermowell, for temperature measurement in non-aggressive fluids use the TH-140 thermowell, in aggressive fluids use the NTH-140 thermowell. Mounting clamps, thermowells and protective coils are not included in the scope of delivery and must be ordered separately.


Number of outputs2, 2
Number of control ranges1
Output signalswitching
External settingNo
Rated impulse voltage4000 V
Diameter sensor element9.5 mm
Electric connectionscrew terminals
Electronic controlNo
With explosion protectionNo
Colourgrey
Sensor elementcapillary tube
Function type (systems engineering)TW, TW
Device versionsurface-mounted unit
Internal settingYes
Contact interlockingNo
Bearing temperature–10 … 55 °C
Length of sensor76 mm
Capillary length1.8 m
Max. air humidity (non-condensing)95 % r.H.
Sensor materialCu
Housing materialplastic
Max. Sensor temperature200 °C
Max. switching voltage230 VAC, 50 Hz
Max. switching current15 (8) A
MediumAir
Min. switching voltage24 VAC, 50 Hz
Min. switching current150 mA
Mounting/attachmentwall mounting
Surface finishmatt, matt
Control range-10 … 12 °C, -10 … 12 °C
Heating control function
Cooling control function
Switching differentialHeating/cooling: 1 K
Switching difference, can be adjustedNo
Switching elementmicroswitch
Switching contacttwo-way contact
Potential free switching contactYes
Switching power3450 W
Protection classIP65, IP65
Protection classI
Safety and EMCin accordance with DIN EN 60730
ScaleDegree Celsius
Ambient temperature−10 … 55 °C
Degree of contamination2
Dimensions (W x H x D)120 mm x 200 mm x 75 mm

Loading specification text...

PhotoTypeArt. no.Features
SW-200-12SW-200-12C1809220Protective coil, 200 mm, nickel-plated steel, inner x outer diameter 11 x 17 mm, cable…View product
TH-140TH-140C1809409Thermowell, 140 mm, nickel-plated brass, diameter inside x outside 10 x 12 mmView product
NTH-140NTH-140C1809435Thermowell, 140 mm, V4A (1.4571), diameter inside x outside 10 x 12 mmView product
JZ-04JZ-04E6160133Capillary tube feed-through for JTF frost protection thermostats and JMT/WR/JET capillary regulatorsView product
JZ-05/1MJZ-05/1MC1809462Single mounting bracketView product
JZ-05/6MJZ-05/6MC1809474Mounting clips (metal) 6 pcs.View product
JZ-05/6KJZ-05/6KC1809536Mounting clips (plastic) 6 pcs.View product
JZ-07JZ-07E6160145Mounting bracketView product