Skip to main content

Differential pressure switch, 400…1600Pa, internal setting

JDW-10

Differential pressure switch, 400…1600Pa, internal setting

Differential pressure switch for monitoring overpressure, differential pressure, or underpressure of air and non-flammable, non-aggressive gases. Can be used as a fume cupboard or fan monitor or flow monitor to protect electrical heating coils, as a filter monitor, air pressure deficiency protection, or limit controller. Note: Once the differential pressure switch has switched a voltage > 24 V and a current > 0.1 A, the gold layer on the contacts is burnt away. After that, the differential pressure switch can only be operated with this or a higher power. Note: The hose set JZ-06 / 1 is not included in the scope of delivery and must be ordered separately.
Delivery without mounting bracket, can be screwed on directly (using 2 screws).
  • Art.-Nr.: H530997

    Technical data

    Ambient temperature, lower value -15 °C
    Ambient temperature, upper value 80 °C
    Bearing temperature, lower value 15 °C
    Bearing temperature, upper value 80 °C
    Colour Black
    Control function, overpressure or underpressure Yes
    Control range, pressure (lower value) 400 Pa
    Control range, pressure (upper value) 1600 Pa
    Degree of contamination 2
    Depth 46,5 mm
    Electric connection Screw terminals
    Electronic version No
    External setting No
    Function type (systems engineering) Monitor
    Height 86 mm
    Housing material Plastic
    Internal setting Yes
    Max.pressure 5000 Pa
    Maximum air humidity (non-condensing) 95 % r.H
    Maximum switching current 1,5 (0,4) AAC, 1 (0,2) ADC
    Maximum switching voltage 230 V AC , 50 Hz / 24 V DC
    Medium Air, not aggressive
    Medium temperature -15 °C
    Minimum switching current 1 mA
    Minimum switching voltage 12 V AC, 50 Hz 12 V DC
    Mounting / attachment Wall mounting
    Number of control ranges 1
    Number of outputs 2
    Operating voltage None
    Operation Internal setpoint adjuster
    Output signal Switching
    Potential free switching contact Yes
    Pressure connection 6,2 mm
    Protection class II, following appropriate mounting
    Safety and EMC In accordance with DIN EN 60730
    Sensor element Pressure membrane
    Surface properties Matt
    Switching contact Two-way contact
    Switching difference Approx. 30…60 Pa
    Switching element Microswitch
    Switching power 345 WAC, 24 WDC
    Type of protection IP54
    Width 90 mm
    With explosion protection No
    Circuit diagram  Circuit diagram

    Downloads

    Instructions

    Datasheet

    Photo Type Articlenumber Features Kind
    JZ-06/1 H5309229 Connection set for differential pressure switch JDW/JDL Accessories
    JZ-10 H5309237 Mounting bracket for JDL 109/-113 and JDW-3/-5/-10, with 6 screws Accessories
     

    Contact request

      This form is currently undergoing maintenance. Please try again later.

    Do you have questions or are you interested in our products?

    Please contact the electrician you trust or write us a message.

    Close Menu