Control room double thermostat, 2x -10…40…°C, 2x TW, 2x internal setting

Control room double thermostat, 2x -10…40…°C, 2x TW, 2x internal setting

Colour: anthracite grey (similar to RAL 7016), transparent front, sensor material: V4A, max. sensor temperature: Full scale value +15 %, max. head temperature: 50 …°C, permissible air humidity: max. 95 % r. H., non-condensing, operating voltage: none, max. switching current: NC contact: 16 (2.5) A at 230 V AC + 10 %, 0.25 A at 230 V DC + 10 %, NO contact: 6.3 (2.5) A at 230 V AC + 10 %, 0.25 A at 230 V DC + 10 %, min. switching current: at 24 V (AC / DC) min. 100 mA, max. switching current: 230 V AC 50 / 60 Hz, 230 V DC, min. switching current: 24 V AC / 50 Hz, 24 V DC, switching element: Microswitch, switching contact: Two-way contact, potential-free, control function: Heating or cooling, heating and cooling, hysteresis: 1.3 K, electric connection: Push-in terminal, mounting / attachment: Wall mounting, protection class: I, type of protection: IP54 (optional IP 65), safety and EMC: according to DIN EN 60730 (VDE 0631), sensor: liquid-filled capillary, general features: Degrees Celsius scale, 2x -10…40…°C, 2x TW, 2x internal setting
Product inquiry
  • Art.-Nr.: KA011100

    Technical data

    suitable as monitorJa
    suitable as 2-point controllerNein
    suitable as cut-outNein
    process temperature50°C
    control range, upper value0°C
    control range, lower value50°C
    switching difference1.3 K
    device versionsurface-mounted unit
    medium temperature (EF007506)57°C
    sensor elementcapillary tube
    number of two-way contacts2
    electric connectionPush in Klemme
    type of protectionIP54
    electronic versionNein
    with explosion protectionNein
    number of outputs2
    number of control ranges2
    output signalswitching
    external settingNein
    operating voltagekeine
    setting range, upper value0°C
    setting range, lower value50°C
    colouranthr. grey (RAL7016), front side transp.
    materialKunststoff
    function type (systems engineering)TW/TW
    bearing temperature, upper value80°C
    bearing temperature, lower value-30°C
    max. sensor temperature57°C
    maximum switching voltage230 V AC 50 / 60 Hz, 230 V DC
    maximum switching currentNC con.: 16 (2.5) A; NO con.: 6.3 (2.5) A
    mediumair, not aggressive
    minimum switching voltage24 V AC / 50 Hz, 24 V DC
    minimum switching currentat 24 V (AC/DC) min. 100 mA
    mounting / attachmentWandmontage
    potential free switching contactJa
    heating or cooling control functionJa
    switching elementmicroswitch
    switching contact2 two-way contacts
    protection classI
    EMC safetyin accordance with DIN EN 60730
    scaledegrees Celsius
    ambient temperature, upper value50°C
    ambient temperature, lower value0°C
    maximum air humidity (non-condensing)95% r.H
    switching difference, can be adjustedNein
    contact interlockingNein
    height146,8mm
    width170mm
    depth57,5mm
    can be read offJa
    with displayJa
    external temperature compensatedNein
    medium temperature up to (EF007369)57°C
    medium temperature (EF007369)-30°C
    heating and cooling control functionJa
    internal settingJa
    2nd control range, lower value0°C
    2nd control range, upper value50°C
    max. operating pressure50°C
    external resetNein
    Circuit diagramKA011100 Circuit diagram

    Downloads

     

    Contact request

     

    Do you have questions or are you interested in our products?

    Please contact the electrician you trust or write us a message.