The KTRRB-117.128 climate controller has been developed especially for controlling convector fans, fan coil devices and other fan-assisted air-conditioning systems in 2- or 4-pipe systems with closed when de-energised valves. In this case, the KTRRB-117.128 is used as a single-room thermostat with internal sensor or as an external control device with optional remote sensor. The optional external upstream sensor is used for automatic changeover of the controller in heating or cooling mode in 2-pipe operation depending on the inlet temperature; alternatively, this input may be used as a H/C changeover contact. In the event of a sensor failure or short circuit, the heating is controlled with a duty cycle of 30% in order to prevent cooling down or frost damage in the room. Using an internal switch, the existing contact input can be configured as an ECO contact or standby contact. ECO function: When this function is selected, in heating mode the temperature is reduced by 3K and in cooling mode increased by 3K. Standby function: When this function is selected, the controller is switched off (frost protection still active). Surface mounting / wall mounting or using an adapter plate on a flush-mounted socket.
Art.-Nr.: MA601300
Technical data
Actual temperature display | No |
Additional heating switch | No |
Ambient temperature, lower value | 0 °C |
Ambient temperature, upper value | 40 °C |
Assembly | Complete device |
Bearing temperature, lower value | -20 °C |
Bearing temperature, upper value | 70 °C |
Colour | Pure white |
Control behaviour | 2-point |
Control range, lower value | 5 °C |
Control range, upper value | 30 °C |
Cooling control function | Yes |
Degree of contamination | 2 |
Depth | 26 mm |
Design | Berlin 3000 |
Display | No |
ECO function (reduction) | Yes |
ECO temperature reduction | Approx. 3 K |
Electric connection | Screw terminals |
Electronic control | Yes |
Energy efficiency class | I |
External setting | Yes |
Fan switch 3-stage | Yes |
Heating / cooling switch | No |
Heating control function | Yes |
Height | 110,7 mm |
Housing material | Plastic ABS |
Maximum air humidity (non-condensing) | 95 % r.H |
Maximum switching current | 625 mA |
Maximum switching voltage | 230 V AC, 50 Hz |
Mechanical range reduction | Yes |
Minimum switching voltage | 230 V AC / 50 Hz |
Mounting / attachment | Surface mounting |
Neutral zone | Approx. 2 K |
Number of control ranges | 1 |
Number of outputs | 3 |
Number of outputs, cooling | 1 |
Number of outputs, heating | 1 |
Off / fan man / fan auto switch | No |
On / Off switch | Yes |
Operating voltage | 230 V AC / 50 Hz |
Operation | Rotary knob and switches |
Output signal | 48 V AC, 50 Hz / 60 V DC |
Potential free switching contact | No |
Protection class | II, following appropriate mounting |
RAL colour number (similar) | 9010 |
Safety and EMC | In accordance with DIN EN 60730 |
Scale | Degree Celsius |
Sealable | No |
Sensor element | NTC internal, optional NTC external |
Sensor external | No |
Surface properties | Matt |
Switch/lamp night-time reduction | No |
Switching difference | Approx. 1 K |
Switching difference, can be adjusted | No |
Temperature controller version | Climate controller |
Thermal feedback | No |
Type of protection | IP30 |
Width | 110 mm |
With explosion protection | No |