Skip to main content

Room hygrostat, surface-mounted, 24V AC to 230V AC, 35…85% r.H., two-way contact, internal setting

RFHSB-060.011

Room hygrostat, surface-mounted, 24V AC to 230V AC, 35…85% r.H., two-way contact, internal setting

The room hygrostat is used to monitor and control relative humidity, e.g. in business premises, apartments, conservatories, bathrooms, swimming pools, computer rooms and other spaces with a clean, non-aggressive environment. Relative humidity acting on a measuring strip activates a potential-free switch contact. Its internal setpoint setting makes it especially suitable for public authorities, schools and similar public buildings.
  • Art.-Nr.: MA020203

    Technical data

    Ambient temperature, lower value0 °C
    Ambient temperature, upper value60 °C
    AssemblyComplete device
    Bearing temperature, lower value-20 °C
    Bearing temperature, upper value70 °C
    Can be read offNo
    ColourPure white
    Connection cross-section0,5 mm² – 2,5 mm²
    Contact interlockingNo
    Cooling control functionNo
    Degree of contamination2
    Depth25,5 mm
    DesignBerlin 2000
    Digital displayNo
    DisplayNo
    Electric connectionScrew terminals
    External settingNo
    Heating control functionNo
    Height83,4 mm
    Housing materialPlastic ABS
    Humidify / dehumidify control functionYes
    Internal settingYes
    Maximum air humidity (non-condensing)95 % r.H
    Maximum switching currentE: 5 (0,2) A ; B: 2 (0,2) A
    Maximum switching voltage230 V AC, 50 Hz
    Mechanical range reductionNo
    MediumAir, not aggressive
    Minimum switching current100 mA
    Minimum switching voltage24 V AC / 50 Hz
    Mounting / attachmentSurface mounting
    NEMA type of protectionOther
    Number of outputs2
    On / Off switchNo
    Operating voltageNone
    OperationInternal setpoint adjuster
    Output signalSwitching (230 V AC / 24 V AC, 50 Hz)
    Potential free switching contactNo
    Protection classII, following appropriate mounting
    RAL colour number (similar)9010
    Safety and EMCIn accordance with DIN EN 60730
    SealableNo
    Sensor elementPlastic fibres
    Setting range, rel. air humidity lower value35 %
    Setting range, rel. air humidity upper value85 %
    Surface propertiesMatt
    Switching contactTwo-way contact
    Switching differenceApprox. 7% r.H.
    Switching difference, can be adjustedNo
    Switching elementMicroswitch
    Switching power1150 W bzw. 460 W
    Type of protectionIP30
    Width78,3 mm
    With explosion protectionNo
    With thermostatNo