Skip to main content

Room hygrostat, surface-mounted, 24V AC or 230V AC, 10…35…°C, 30…100% r.H., two-way contact

RKDSB-171.000

Room hygrostat, surface-mounted, 24V AC or 230V AC, 10…35…°C, 30…100% r.H., two-way contact

Hygrothermostat for simultaneous control or monitoring of temperature and humidity in offices, residential properties and hotels, as well as swimming pools, conservatories and residential baths and suitable for all types of heating. The device can be operated using 24 V~ or 230 V~ as required. With electric underfloor heating, ensure that the output from the heating cannot overheat the screed, even during continuous operation. With hot water heating systems, a max. of 10 valves (closed when de-energised) should be connected to the heating output, or a max. of 5 valves (open when de-energised) to the cooling output. When cooling, a max. of 5 valves (closed when de-energised) should be connected to the cooling output, or a max. of 10 valves (open when de-energised) to the heating output. Where necessary, thermal cut-outs may also need to be installed. Max. switching current: Dehumidifying (terminal 9) 5 (0.2) A, humidifying (terminal 8) 3 (0.2) A, heating (terminal 1) 10 (4) A at 230 V AC / 1 (1) A at 24 V AC, cooling (terminal 2) 5 (2) A at 230 V AC / 1 (1) A at 24 V AC, switching power: Terminal 9: 1150 W, terminal 8: 690 W, terminal 1: 2300 W at 230 V AC / 24 W at 24 V AC, terminal 2: 1150 W at 230 V AC / 230 W at 24 V AC
  • Art.-Nr.: MA220000

    Technical data

    Ambient temperature, lower value 0 °C
    Ambient temperature, upper value 50 °C
    Assembly Complete device
    Bearing temperature, lower value -20 °C
    Bearing temperature, upper value 60 °C
    Can be read off No
    Colour Pure white
    Contact interlocking No
    Control range, lower value 10 °C
    Control range, upper value 35 °C
    Cooling control function Yes
    Degree of contamination 2
    Depth 26 mm
    Design Berlin 3000
    Digital display No
    Display No
    Electric connection Screw terminals
    External setting Yes
    Heating control function Yes
    Height 110,7 mm
    Housing material Plastic ABS
    Humidify / dehumidify control function Yes
    Internal setting No
    Maximum air humidity (non-condensing) 95 % r.H
    Maximum switching current 10 (4) A
    Maximum switching voltage 230 V AC, 50 Hz
    Mechanical range reduction Yes
    Medium Air, not aggressive
    Minimum switching current 100 mA
    Minimum switching voltage 24 V AC / 50 Hz
    Mounting / attachment Surface mounting
    NEMA type of protection Other
    Number of outputs 6
    On / Off switch Yes
    Operating voltage 230 V AC / 50 Hz or 24 V AC / 50 Hz
    Operation Rotary knob and switches
    Output signal Switching
    Potential free switching contact No
    Protection class II, following appropriate mounting
    RAL colour number (similar) 9010
    Safety and EMC In accordance with DIN EN 60730
    Sealable No
    Sensor element Plastic fibres and bimetal
    Setting range, rel. air humidity lower value 30 %
    Setting range, rel. air humidity upper value 100 %
    Surface properties Matt
    Switching contact 2 two-way contacts
    Switching difference Approx. 4% r.H. approx. 1 K
    Switching difference, can be adjusted No
    Switching element Microswitch and bimetal
    Switching power 2300 W
    Type of protection IP30
    Width 110 mm
    With explosion protection No
    With thermostat Yes
    Circuit diagram  Circuit diagram

    Downloads

    Instructions

    Datasheet

    Photo Type Articlenumber Features Kind