Capillary thermostat, wall mounting, 40…100…°C, external setting, external resetting, capillary length 1.8m

Capillary thermostat, wall mounting, 40…100…°C, external setting, external resetting, capillary length 1.8m

Product inquiry
  • Art.-Nr.: JA042300

    Technical data

    suitable as monitorNein
    suitable as 2-point controllerNein
    suitable as cut-outJa
    max. operating pressure55°C
    adjustable switch-on temperature40°C
    adjustable switch-off temperature100°C
    switching difference8 K
    device versionsurface-mounted unit
    medium temperature (EF007506)115°C
    number of NO contacts0
    number of NC contacts0
    number of two-way contacts1
    electric connectionSchraub-Steckklemmen
    type of protectionIP65
    NEMA type of protectionother
    electronic versionNein
    with explosion protectionNein
    number of outputs2
    number of control ranges1
    output signalswitching
    operating voltagekeine
    setting range, upper value100°C
    setting range, lower value40°C
    RAL colour number (similar)7016/7035
    diameter9,6mm
    length of sensor122mm
    function type (systems engineering)TB
    internal settingNein
    length of supply line1,8m
    bearing temperature, upper value55°C
    bearing temperature, lower value-20°C
    materialKunststoff
    max. sensor temperature110°C
    maximum switching voltage230 V AC, 50 Hz
    maximum switching current15 (8) A
    mediumair, not aggressive
    minimum switching voltage24 V AC / 50 Hz
    minimum switching current150 mA
    mounting / attachmentWandmontage
    surface propertiesmatt
    potential free switching contactJa
    control range, upper value100°C
    control range, lower value40°C
    heating or cooling control functionJa
    switching elementmicroswitch
    switching contacttwo-way contact
    switching power3450 W
    protection classI
    EMC safetyin accordance with DIN EN 60730
    scaledegrees Celsius
    operationDrehknopf
    ambient temperature, upper value55°C
    ambient temperature, lower value-20°C
    degree of contamination2
    maximum air humidity (non-condensing)95% r.H
    external settingJa
    sensor elementcapillary tube
    width83mm
    depth69mm
    Circuit diagramJA042300 Circuit diagram

    Downloads

    PhotoTypeArticlenumberFeaturesKind
    SW-200-12C1809220Protective coil, 200mm, nickel-plated steel, inner x outer diameter 11x17mm, cable entry 11.8mmAccessories
    TH-140C1809409Immersion sleeve, 140mm, nickel-plated brass, inner x outer diameter 10x12mmAccessories
    NTH-140C1809435Immersion sleeve, 140mm, V4A (1.4571), inner x outer diameter 10x12mmAccessories
    JZ-04E6160133Capillary tube duct for JTF frost protection thermostats and JMT/WR/JET capillary controllersAccessories
     