Capillary thermostat, wall mounting, 100…280…°C, external setting, external resetting, capillary length 1.8m

JET-153

Capillary thermostat, wall mounting, 100…280…°C, external setting, external resetting, capillary length 1.8m

Monitoring or control of temperatures of non-aggressive, liquid and gaseous media. Especially suitable for wall mounting. For temperature control of non-aggressive gases in the duct, use the thermowell SW-200-12, for temperature control in non-aggressive fluids use the thermowell TH, in aggressive fluids use the thermowell NTH. Thermowells or protection coils are not included in the scope of delivery.
  • Art.-Nr.: JA044300

    Technical data

    Ambient temperature, lower value -20 °C
    Ambient temperature, upper value 55 °C
    Bearing temperature, lower value -20 °C
    Bearing temperature, upper value 55 °C
    Capillary length 1,8 m
    Colour Grey
    Control range, lower value 100 °C
    Control range, upper value 280 °C
    Cooling control function Yes
    Degree of contamination 2
    Device version Surface-mounted unit
    Diameter sensor element 6 mm
    Electric connection Screw terminals
    Electronic control No
    External setting Yes
    Function type (systems engineering) TB
    Heating control function Yes
    Housing material Plastic
    Internal setting No
    Length of sensor 80 mm
    Max. sensor temperature 320 °C
    Maximum air humidity (non-condensing) 95 % r.H
    Maximum switching current 15 (8) A
    Maximum switching voltage 230 V AC, 50 Hz
    Mechanical range reduction Yes
    Medium Gas / liquid substances (not aggressive)
    Minimum switching current 150 mA
    Minimum switching voltage 24 V AC / 50 Hz
    Mounting / attachment Wall mounting
    Number of control ranges 1
    Number of outputs 2
    Operating voltage None
    Operation Rotary knob, reset button
    Output signal Switching
    Potential free switching contact Yes
    Protection class I
    RAL colour number (similar) 7016/7035
    Rated impulse voltage 4000 V
    Safety and EMC In accordance with DIN EN 60730
    Scale Degree Celsius
    Sensor element Capillary tube
    Sensor material Cu (capillaries made from V2A)
    Surface properties Matt
    Switching contact Two-way contact
    Switching difference, can be adjusted No
    Switching element Microswitch
    Switching power 3450 W
    Type of protection IP65
    With explosion protection No
    Circuit diagram  Circuit diagram

    Downloads

    Instructions

    Datasheet

    Photo Type Articlenumber Features Kind
    TH-280 C1809440 Immersion sleeve, 280mm, nickel-plated brass, inner x outer diameter 8x10mm Accessories
    NTH-200 C1809439 Immersion sleeve, 200mm, V4A (1.4571), inner x outer diameter 8x10mm Accessories
    NTH-280 C1809441 Immersion sleeve, 280mm, V4A (1.4571), inner x outer diameter 8x10mm Accessories
    SW-200-12 C1809220 Protective coil, 200mm, nickel-plated steel, inner x outer diameter 11x17mm, cable entry 11.8mm Accessories
    TH-100 C1809310 Immersion sleeve, 100mm, nickel-plated brass, inner x outer diameter 8x10mm Accessories
    TH-200 C1809438 Immersion sleeve, 200mm, nickel-plated brass, inner x outer diameter 8x10mm Accessories
    JZ-04 E6160133 Capillary tube duct for JTF frost protection thermostats and JMT/WR/JET capillary controllers Accessories
    NTH-100 C1809308 Immersion sleeve, 100mm, V4A (1.4571), inner x outer diameter 8x10mm Accessories
     

    Contact request

      This form is currently undergoing maintenance. Please try again later.

    Do you have questions or are you interested in our products?

    Please contact the electrician you trust or write us a message.

    Close Menu