Built-in duct temperature sensor, PT1000, installation length 115mm

The EKF installation duct sensors are used to measure temperatures in liquids and gases in pipes, air ducts or containers. The mounting flange (MF) is required for use in air ducts. Nickel-plated brass thermowells (THMs) must be used for use in liquids. Immersion sleeves made of stainless steel V4A (THV) are recommended for aggressive media. Thermowells or mounting flanges are not included in the scope of delivery and must be ordered separately as accessories.
  • Art.-Nr.: G9140150

    Technical data

    Active temperature measurement No
    Ambient temperature −30 … 70 °C
    Bearing temperature –30 … 70 °C
    Colour pure white
    Connection cross-section 0,14 – 2,5 mm²
    Cover fastening bayonet fastening
    Dimensions (W x H x D) 58 mm x 64 mm x 149 mm
    Electric connection screw terminals
    Housing material plastic PA
    Length of sensor 100 mm
    Max. air humidity (non-condensing) 95 % r.H.
    Montage/Befestigung in imm. sleeve, prot. coil, on tube, etc
    Passive temperature measurement Yes
    Plug-in length 115 mm
    Protection class III
    RAL colour number (similar) 9010
    Safety and EMC in accordance with DIN EN 60730
    Sensor element PTC internal
    Sensor element inside the housing No
    Sensor element outside the housing Yes
    Sensor type PT-1000
    Suitable for duct mounting Yes
    Suitable for fluids Yes
    Suitable for gases Yes
    Suitable for pipe mounting Yes
    Surface finish gloss
    Version of sensor temperature sensor for gases/liquids
    With explosion protection No
    With housing Yes
    With supply line No