Skip to main content

Frost protection thermostat, capillary length 1.8m, external setting, external reset

JTF-4

Frost protection thermostat, capillary length 1.8m, external setting, external reset

For protecting hot water heating registers against freezing. The device is intrinsically safe and has a sealable setpoint adjustment. For temperature measurement of non-aggressive gases in the duct, use the SW-200-12 thermowell, for temperature measurement in non-aggressive fluids use the TH-140 thermowell, in aggressive fluids use the NTH-140 thermowell. Mounting clamps, thermowells and protective coils are not included in the scope of delivery and must be ordered separately.
  • Art.-Nr.: E6090310

    Technical data

    Ambient temperature −10 … 55 °C
    Bearing temperature –10 … 55 °C
    Capillary length 1.8 m
    Colour grey
    Contact interlocking Yes
    Control range -10 … 12 °C
    Cooling control function Yes
    Degree of contamination 2
    Device version surface-mounted unit
    Diameter sensor element 9.5 mm
    Dimensions (W x H x D) 105 mm x 112 mm x 55 mm
    Electric connection screw terminals
    Electronic control No
    External reset Yes
    External setting Yes
    Function type (systems engineering) TB
    Heating control function Yes
    Housing material plastic
    Internal setting No
    Length of sensor 76 mm
    Max. air humidity (non-condensing) 95 % r.H.
    Max. Sensor temperature 200 °C
    Max. switching current 15 (8) A
    Max. switching voltage 230 VAC, 50 Hz
    Medium Air
    Min. switching current 150 mA
    Min. switching voltage 24 VAC, 50 Hz
    Montage/Befestigung wall mounting
    Number of control ranges 1
    Number of outputs 2
    Output signal switching
    Potential free switching contact Yes
    Protection class I
    Rated impulse voltage 4000 V
    Safety and EMC in accordance with DIN EN 60730
    Scale Degree Celsius
    Sensor element capillary tube
    Sensor material Cu
    Surface finish matt
    Switching contact two-way contact
    Switching difference, can be adjusted No
    Switching differential manual reset according to 4 K (Heating/cooling)
    Switching element microswitch
    Switching power 3450 W
    With explosion protection No