Skip to main content

Universal capillary thermostat, 20…150°C, hysteresis -10…-15K, TB, internal setting, external reset

RTKSA-002.310

Universal capillary thermostat, 20…150°C, hysteresis -10…-15K, TB, internal setting, external reset

This series of devices has been specially developed for use in heating technology in boiler systems or storage tanks, district heating transfer stations and heat transfer systems, in ventilation technology as supply air monitoring or as limiters for electric heating registers and for controlling and monitoring temperatures on pipes and tanks. Thermowells, protective coils and fixing set are not included in the scope of delivery. The fixing set JZ-29 must be used in conjunction with thermowells or protective coils. When used as a contact regulator (pipe mounting), the fixing set JZ-31 must be used.
  • Art.-Nr.: KA000201

    Technical data

    Bearing temperature –30 … 80 °C
    Capillary length 2 m
    Colour anthracite
    Contact interlocking Yes
    Control range 20 … 150 °C
    Cooling control function Yes
    Device version surface-mounted unit
    Diameter sensor element 6 mm
    Dimensions (W x H x D) 53 mm x 146,8 mm x 53 mm
    Electric connection Push-in clamp
    Electronic control No
    External reset Yes
    External setting No
    Function type (systems engineering) TB
    Heating control function Yes
    Internal setting Yes
    Length of sensor 55 mm
    Max. air humidity (non-condensing) 95 % r.H.
    Max. Sensor temperature 177 °C
    Max. switching current 16 (2,5) A, 0,25 A, 2 (0,4) A, 0,25 A
    Max. switching voltage 230 VAC, 50/60 Hz / 230 VDC
    Min. switching current at 24 V (AC/DC) min. 100 mA
    Min. switching voltage 24 VAC, 50 Hz / 24 VDC
    Montage/Befestigung in imm. sleeve, prot. coil, on tube, etc
    Number of control ranges 1
    Number of outputs 2
    Operation internal setpoint adjuster
    Output signal switching
    Potential free switching contact Yes
    Protection class I
    Safety and EMC in accordance with DIN EN 60730
    Scale Degree Celsius
    Sensor element capillary tube
    Sensor material Cu
    Switching contact two-way contact
    Switching difference, can be adjusted No
    Switching differential manual reset according to -10 … -15 K (Heating/cooling)
    Switching element microswitch
    With explosion protection No