Skip to main content

Universal capillary double thermostat, TW 0…120…°C, TW 0…120…°C, hysteresis 2x 3K

RTKSA-014.210

Universal capillary double thermostat, TW 0…120…°C, TW 0…120…°C, hysteresis 2x 3K

This series of devices was specially developed for use in heating technology in boiler systems or storage tanks, district heating transfer stations and heat transfer systems, in ventilation technology as supply air monitors or as limiters for electric heating registers. Immersion sleeves/protection coils are not included in the scope of delivery. The JZ-30 accessory must be used in conjunction with immersion sleeves or protection coils.
The control range / hysteresis for both temperature monitors is 0… 120 ° C / 3K.
  • Art.-Nr.: KA001100

    Technical data

    Ambient temperature, upper value 80 °C
    Bearing temperature, lower value -30 °C
    Bearing temperature, upper value 80 °C
    Capillary length 2 m
    Colour Anthr. grey (RAL7016), frontp. transp.
    Contact interlocking No
    Control range, lower value 0 °C
    Control range, upper value 120 °C
    Cooling control function Yes
    Depth 57,5 mm
    Device version Surface-mounted unit
    Diameter sensor element 6 mm
    Electric connection Push-in terminal
    Electronic control No
    External reset No
    Function type (systems engineering) TW/TW
    Heating control function Yes
    Height 146,8 mm
    Internal setting Yes
    Max. sensor temperature 138 °C
    Maximum air humidity (non-condensing) 95 % r.H
    Maximum switching current O: 16 (2,5) A; S: 6,3 (2,5) A, 0,25 ADC
    Maximum switching voltage 230 V AC 50 / 60 Hz, 230 V DC
    Minimum switching current At 24 V (AC/DC) min. 100 mA
    Minimum switching voltage 24 V AC / 50 Hz, 24 V DC
    Mounting / attachment In imm. sleeve, prot. coil, on tube, etc
    Number of control ranges 2
    Number of outputs 4
    Operating voltage None
    Operation Internal setpoint adjuster
    Output signal Switching
    Potential free switching contact Yes
    Protection class I
    Safety and EMC In accordance with DIN EN 60730
    Scale Degree Celsius
    Sensor element Capillary tube
    Sensor material Cu
    Switching contact 2 two-way contacts
    Switching difference TW: 3 K ; TW 3K
    Switching difference, can be adjusted No
    Switching element Microswitch
    Type of protection IP54
    Width 106 mm
    With explosion protection No
    Circuit diagram  Circuit diagram

    Downloads

    Info sheet

    Assembly instructions

    Datasheet

    Photo Type Articlenumber Features Kind
    JZ-30 KA999902 Fastening set for RTKSA THK/NTHK/SWK double controller Accessories
    JZ-33 KA999904 Sealing set for universal capillary thermostats RTKSA-xxx.xxx Accessories
     

    Contact request

      This form is currently undergoing maintenance. Please try again later.

    Do you have questions or are you interested in our products?

    Please contact the electrician you trust or write us a message.