Skip to main content

Frost protection thermostat, 3m, IP65, hysteresis +3K, STB, indoor setting, outdoor reset

RTKSA-203.120

Frost protection thermostat, 3m, IP65, hysteresis +3K, STB, indoor setting, outdoor reset

The RTKSA frost protection regulators have been specially developed for air or water-side frost protection of hot water heating coils and heat exchangers in ventilation, heating or air conditioning systems. The capillaries are active along their entire length. The device responds when the minimum response length of the capillary (15 cm) reaches the set scale value. In the event of a sensor break, contact 1-2 is permanently open and contact 1-4 is permanently closed. Unlocking is no longer possible. Note: Mounting clamps, thermowells and protective coils are not included in the scope of delivery and must be ordered separately. Air-side application: For frost protection of heating registers, the capillary is clamped in front of the heating register to be protected with mounting clamps. The JZ-05/6M (metal) or JZ-05/6 K (plastic) mounting clamps must be used for this purpose.
  • Art.-Nr.: KA020302

    Technical data

    Bearing temperature –30 … 80 °C
    Capillary length 3 m
    Colour anthracite
    Contact interlocking Yes
    Control range -10 … 15 °C
    Cooling control function Yes
    Device version surface-mounted unit
    Dimensions (W x H x D) 53 mm x 146,8 mm x 57,5 mm
    Electric connection Push-in clamp
    Electronic control No
    External reset Yes
    External setting No
    Function type (systems engineering) STB
    Heating control function Yes
    Internal setting Yes
    Max. air humidity (non-condensing) 95 % r.H.
    Max. Sensor temperature 120 °C
    Max. switching current 16 (2,5) A, 0,25 A, 2 (0,4) A, 0,25 A
    Max. switching voltage 230 VAC, 50/60 Hz / 230 VDC
    Min. switching current at 24 V (AC/DC) min. 100 mA
    Min. switching voltage 24 VAC, 50 Hz / 24 VDC
    Montage/Befestigung wall mounting
    Number of control ranges 1
    Number of outputs 2
    Operation internal setpoint adjuster, reset button
    Output signal switching
    Potential free switching contact Yes
    Protection class I
    Safety and EMC in accordance with DIN EN 60730
    Scale Degree Celsius
    Sensor element capillary tube
    Sensor material Cu
    Switching contact two-way contact
    Switching difference, can be adjusted No
    Switching differential manual reset according to 3 K (Heating/cooling)
    Switching element microswitch
    With explosion protection No

    Downloads

    Assembly instructions

    Sales brochure

    Datasheet

    Photo Type Articlenumber Features Kind
         

    Kontaktanfrage

        This form is currently undergoing maintenance. Please try again later.    

    Do you have questions or are you interested in our products?

    Please contact the electrician you trust or write us a message.

    Close Menu