RTKSA-204.020
Frost protection thermostat, 1.8m, IP65, hysteresis 1.5K, STW, internal setting, external resetting
The RTKSA frost protection controllers were specially developed for air or water-side frost protection of hot water heater registers and heat exchangers in ventilation, heating or air conditioning systems. If the sensor breaks, contact 1 – 2 is permanently opened and contact 1 – 4 is permanently closed. Note: Mounting brackets, immersion sleeves and protective coils are not included in the scope of delivery and must be ordered separately. Air-side application: The SWK-2-xxx protective coils can be used to measure the temperature of non-aggressive gases in the duct. Water-side application: For temperature measurement in non-aggressive fluids, the immersion sleeves THK-2-xxx and in aggressive fluids the immersion sleeves NTHK-2-xxx can be used.
Art.-Nr.: KA020401
Technical data
Contact request
This form is currently undergoing maintenance. Please try again later.Do you have questions or are you interested in our products?
Please contact the electrician you trust or write us a message.