JTU-50
Duct thermostat, -25…+65°C, hysteresis 1.5K, capillary length 350mm
Minimum or maximum thermostat for supply air monitoring and fan control in ventilation and air conditioning systems. Overheating protection thermostat for electric heating coils and direct-fired air heaters in oil and gas operation.
Art.-Nr.: E6100000
Technical data
Ambient temperature | −15 … 80 °C |
Bearing temperature | –15 … 80 °C |
Burner control range | -25 … 65 °C |
Capillary length | 0.35 m |
Colour | grey |
Cooling control function | Yes |
Degree of contamination | 2 |
Device version | surface-mounted unit |
Dimensions (W x H x D) | 83 mm x 139 mm x 58 mm |
Electric connection | screw terminals |
Electronic control | No |
External reset | No |
Function type (systems engineering) | TW |
Heating control function | Yes |
Housing material | Metal sheet steel |
Internal setting | Yes |
Length of sensor | 350 mm |
Max. air humidity (non-condensing) | 95 % r.H. |
Max. Sensor temperature | 200 °C |
Max. switching current | 15 (8) A |
Max. switching voltage | 230 VAC, 50 Hz |
Medium | Air |
Min. switching current | 150 mA |
Min. switching voltage | 24 VAC, 50 Hz |
Montage/Befestigung | mounting on air duct |
Number of control ranges | 1 |
Number of outputs | 2 |
Operation | internal setpoint adjuster |
Output signal | switching |
Potential free switching contact | Yes |
Protection class | I |
Rated impulse voltage | 4000 V |
Safety and EMC | in accordance with DIN EN 60730 |
Scale | Degree Celsius |
Sensor element | capillary tube |
Sensor material | Cu |
Surface finish | matt |
Switching contact | two-way contact |
Switching difference, can be adjusted | No |
Switching differential | Heating/cooling: 1,5 K |
Switching element | microswitch |
Switching power | 3450 W |
With explosion protection | No |