Skip to main content

Duct thermostat, 20…100…°C, external resetting, capillary length 1250mm

JTU-20

Duct thermostat, 20…100…°C, external resetting, capillary length 1250mm

Minimum or maximum thermostat for supply air monitoring and fan control in ventilation and air conditioning systems. Overheating protection thermostat for electric heating coils and direct-fired air heaters in oil and gas operation.
  • Art.-Nr.: E6100075

    Technical data

    Ambient temperature, lower value -15 °C
    Ambient temperature, upper value 80 °C
    Bearing temperature, lower value -15 °C
    Bearing temperature, upper value 80 °C
    Capillary length 1,25 m
    Colour Grey
    Control range, burner from 20 °C
    Control range, burner up to 100 °C
    Cooling control function Yes
    Degree of contamination 2
    Device version Surface-mounted unit
    Electric connection Screw terminals
    Electronic control No
    External reset Yes
    Function type (systems engineering) STB
    Heating control function Yes
    Housing material Sheet steel
    Internal setting Yes
    Length of sensor 1250 mm
    Max. sensor temperature 200 °C
    Maximum air humidity (non-condensing) 95 % r.H
    Maximum switching current 15 (8) A
    Maximum switching voltage 230 V AC, 50 Hz
    Medium Air, not aggressive
    Minimum switching current 150 mA
    Minimum switching voltage 24 V AC / 50 Hz
    Mounting / attachment Mounting on air duct
    Number of control ranges 1
    Number of outputs 2
    Operating voltage None
    Operation Internal setpoint adjuster, reset button
    Output signal Switching, burner interlocking
    Potential free switching contact Yes
    Protection class I
    Rated impulse voltage 4000 V
    Safety and EMC In accordance with DIN EN 60730
    Scale Degree Celsius
    Sensor element Capillary tube
    Sensor material Cu
    Surface properties Matt
    Switching contact Two-way contact
    Switching element Microswitch
    Switching power 3450 W
    Type of protection IP40
    With explosion protection No
    Circuit diagram  Circuit diagram

    Downloads

    Instructions

    Datasheet

     

    Contact request

      This form is currently undergoing maintenance. Please try again later.

    Do you have questions or are you interested in our products?

    Please contact the electrician you trust or write us a message.

    Close Menu