Dew point sensor for cooling ceilings/pipe, 10m cable

TPS 2

Dew point sensor for cooling ceilings/pipe, 10m cable

This dew point sensor was specially developed in conjunction with an alre dew point monitor (e.g. WFRRN) or chilled ceiling controller (e.g. KTRRB, KTRRU, KTRRUu, KTRVB, KTFRx) to detect and report the dew point. When installed correctly, it prevents condensation dripping from the cooled parts of the cooling circuit. Application: Pipes transporting cold water, plaster cooling ceiling with capillary tube system. Installation/attachment by means of clips on the cooling ceiling capillary tube or with cable ties on the tube. Sensor cable can be extended up to 50 m with 2 x 0.5 mm².
  • Art.-Nr.: G8000300

    Technical data

    Assembly 2 clips for cooling pad, 2 cable ties
    Bearing temperature –20 … 70 °C
    Dimensions (W x H x D) 70 mm x 21,5 mm x 36 mm
    Length of supply line 10 m
    Measurement of dew point Yes
    Montage/Befestigung to cool. ceiling capill. pipe / on pipe
    Protection class IP30
    Version of sensor humidity sensor
    With explosion protection No
    With mounting material Yes
    With supply line Yes