Skip to main content

Air heater thermostat, 70…95…°C (burner), 20…70…°C (fan), 100…°C (STB), capillary length 350mm

JTL-8 NR

Air heater thermostat, 70…95…°C (burner), 20…70…°C (fan), 100…°C (STB), capillary length 350mm

Minimum or maximum thermostat for supply air monitoring and fan control in ventilation and air conditioning systems. Type-tested by TÜV according to DIN EN 14597. For warm air heaters according to DIN 4794. Sensor break: In case of sensor damage or sensor break, contacts 1 and 4 of the fan open. Intrinsic safety/cold protection: The units are intrinsically safe, i.e. if the sensor medium is lost, e.g. due to sensor breakage, the burner is switched off. Since minus temperatures produce the same effect by reducing the volume of the sensor medium, the units are adjusted by means of the "cold screw" in such a way that they only switch off the burner at temperatures below -15 °C. The units can only be switched on again manually at temperatures below -15 °C. The burner is then switched off again. The unit can only be switched back on manually at temperatures higher than approx. - 5 °C using the manual reset button. Overheating protection: The unit protects against uncontrolled overheating, caused e.g. by heat accumulation or by creeping capillary filling loss in the case of invisible damage to the sensor or capillary tube, etc. When a temperature of 220°C is reached, the safety slot in the sensor melts and the unit switches off the burner to the safe side due to loss of filling medium. The burner cannot be switched on again. The unit is then unusable and serves as proof of the existing excess temperature of at least 220°C.
Temperature-controlled fan control, burner monitoring and safety thermal cut-out, 3 functions.
  • Art.-Nr.: E6120038

    Technical data

    Ambient temperature, lower value 15 °C
    Ambient temperature, upper value 80 °C
    Bearing temperature, lower value -15 °C
    Bearing temperature, upper value 80 °C
    Capillary length 0,35 m
    Colour Grey
    Control range, burner from 70 °C
    Control range, burner up to 95 °C
    Control range, fan from 20 °C
    Control range, fan up to 70 °C
    Cooling control function Yes
    Degree of contamination 2
    Device version Surface-mounted unit
    Electric connection Screw terminals
    Electronic control No
    External reset Yes
    Function type (systems engineering) TW/STB
    Heating control function Yes
    Housing material Sheet steel
    Internal setting Yes
    Length of sensor 350 mm
    Max. sensor temperature 200 °C
    Maximum air humidity (non-condensing) 95 % r.H
    Maximum switching current 15 (8) A
    Maximum switching voltage 230 V AC, 50 Hz
    Medium Air, not aggressive
    Minimum switching current 150 mA
    Minimum switching voltage 24 V AC / 50 Hz
    Mounting / attachment Mounting on air duct
    Number of control ranges 2
    Number of outputs 6
    Operating voltage None
    Operation Intern. setpoint adjuster, button, switch
    Output signal Switching
    Potential free switching contact Yes
    Protection class I
    Rated impulse voltage 4000 V
    Safety and EMC In accordance with DIN EN 60730
    Scale Degree Celsius
    Sensor element Capillary tube
    Sensor material Cu
    Surface properties Matt
    Switching contact 3 two-way contacts
    Switching difference 8 K
    Switching element Microswitch
    Switching power 3450 W
    Type of protection IP20
    With explosion protection No
    Circuit diagram  Circuit diagram

    Downloads

    Instructions

    Datasheet

     

    Contact request

      This form is currently undergoing maintenance. Please try again later.

    Do you have questions or are you interested in our products?

    Please contact the electrician you trust or write us a message.

    Close Menu