Art.-No.: H530946
Features:
Flow monitor for 1", mechanical, adjustable, Toggler, 24-230 VAC, 5A
Application:
Technical Data:
Dimensions of housing: | 66 x 30 x 35 mm |
Number of outputs: | 2 |
Output signal: | switching |
Output signal: | switching |
Configuration: | max. flow: 60 l / min |
Rated impulse voltage: | 4000 V |
Operating voltage: | none |
Pressure: | yes |
setting range: | Break point dropping: 13,5...16,5 l / min |
Electrical connection: | 4-pin plug according to DIN EN 175301-803 (previously DIN 43650 - A / ISO 4400) |
Colour of housing: | black |
Sensor: | Flow paddle |
Function type: | Monitors |
Accuracy: | +/- 15% of the set value (switching values only hold good if the flow monitor has been installed in our T-piece If copper T-pieces are used, the switching values will increase.) |
Weight: | ca. 300 |
Hysteresis: | approx. 3,5 l / min |
Internal setting: | yes |
Storage temperature: | -20...70°C |
Scope of supply: | Flow monitor with union nut, MS brazing spout |
Material of housing: | Plastic |
Material of paddle: | Special steel |
Material of carrier: | MS nickel-plated |
max. pressure: | 25 bar |
max. switching voltage: | 230 VAC, 50 Hz |
max. switching current: | 5:00 AM |
Medium: | Fluid, non-aggressive |
min. switching voltage: | 24 VAC, 50 Hz |
min. switching current: | 100 mA at 24 VAC, 50 Hz |
Installation/fastening: | Union nut G 3/8" on brazing spout (for brazing in a standard copper T-piece with outlet 1/2") or T-piece |
Surface quality: | matt |
potential-free: | yes |
control range: | Break point rising: 17,0...20,5 l / min |
Control function: | switches if the set value undershot or exceeded |
Pipe diameter: | 1" / DN25 |
Switching element: | micro switch |
Switching contact: | Changeover |
Switching power: | 1150 W |
Degree of protection: | IP 65 |
Protection class: | II |
Safety and EMC: | according to DIN EN 60730 |
Flow of liquid media: | yes |
Ambient temperature up to: | 70 |
Ambient temperature from: | -20 |
Degree of fouling: | II |
permissible medium temperature: | 110°C |
Permissible atmospheric humidity: | max. 95% r.h., non-condensing |
Ciruit Diagram: | ![]() |