JSF-1E

Art.-No.: JA060100
Features:
Flow monitor for 1...8", mechanical, adjustable, Toggler, 24-230 VAC, 15(8)A
Application:
Technical Data:
Dimensions of housing: | 130 x 71 x 67 mm |
Number of outputs: | 2 |
Output signal: | switching |
Output signal: | switching |
Rated impulse voltage: | 4000 V |
Operating voltage: | none |
Pressure: | yes |
setting range: | The setting and control range depend on the pipe diameter (see the table of switching values in the assembly instructions) |
Electrical connection: | Screw-type terminals |
Colour of housing: | grey (lower part like RAL 7016, upper part like RAL 7035) |
Sensor: | Flow paddle |
Function type: | Monitors |
Accuracy: | +/- 15% of the set value |
Weight: | ca. 900 |
Hysteresis: | depends on the pipe diameter (see the table of switching values in the assembly instructions) |
Internal setting: | yes |
Storage temperature: | -40...85°C |
Scope of supply: | Flow monitor, paddle set |
Material of housing: | Plastic |
Material of paddle: | Special steel |
Material of carrier: | Ms |
max. pressure: | 8 bar |
max. switching voltage: | 230 VAC, 50 Hz |
max. switching current: | 15 (8) A |
Medium: | Fluid, non-aggressive |
min. switching voltage: | 24 VAC, 50 Hz |
min. switching current: | 150 mA at 24 VAC, 50 Hz |
Installation/fastening: | Assembly by means of tapered Whitworth pipe thread R1" |
Surface quality: | matt |
potential-free: | yes |
Test mark/Approbation: | type-tested by the TÜV according to the VdTÜV circular "Flow 100" Component identification no. TÜV S. 04-016 |
Control function: | switches if the set value undershot or exceeded |
Pipe diameter: | 1...8" |
Switching element: | Microswitch |
Switching contact: | Changeover |
Switching power: | 3450 W |
Degree of protection: | IP 65 |
Protection class: | I |
Safety and EMC: | according to DIN EN 60730 |
Flow of liquid media: | yes |
Ambient temperature up to: | 85 |
Ambient temperature from: | -40 |
Degree of fouling: | II |
Accessories: | spare paddle: JZ-09 |
permissible medium temperature: | 120°C |
Permissible atmospheric humidity: | max. 95% r.h., non-condensing |
Ciruit Diagram: | ![]() |