JDW-10

 

: H530997

:
Differential pressure switch, mechanical, 400...1600Pa, monitor, , Toggler, 12-230 VAC, 1,5(0,4)AAC, 12-24 VDC, 1(0,2)ADC, hysteresis 30...60Pa

:
Monitoring of overpressure, differential or under-pressure of air and incombustible, non-aggressive gases. Exhaust or fan monitoring or flow monitor for securing electrical heat registers, as filter monitoring, air pressure shortage safeguard, limit value controller.

JDW-...: Supplied without mounting bracket, can be screwed on directly (with 2 screws).
JDW-...Z: Supplied with attached mounting bracket JZ-10.
JDL-...: Supplied with attached mounting bracket JZ-10.

Note: Once the differential pressure switch has connected a voltage > 24 V and a current > 0,1 A, the gold layer at the contacts will have burnt away. Thereafter, the differential pressure switch can only be operated at this or a higher power.

Note: The hose set is not a part of the delivery scope and must be ordered separately.

:

:86 x 46,5 x 90 mm
:2
:1
:switching
:switching
:4000 V
:none
:
:6,2 mm
:1600
:all data in Pa
:400
:Screw-type terminals
:black
:Pressure membrane
:Monitors
:approx. 30...60 Pa depending on the setting range
:
:-15...+80 °C
:Differential pressure switch
:Plastic
:5000 Pa
:80
:230 VAC, 50 Hz 24 VDC
:1,5 (0,4) AAC 1 (0,2) ADC
:Air, not aggressive
:12 VAC, 50 Hz 12 VDC
:1 mA
:Wall mounting
:matt
:
:1600
:400
:switches if the pressure is undershot or overshot
:Microswitch
:Toggler, gold contact
:345 WAC, 24 WDC
:IP 54
:II
:according to DIN EN 60730
:
:80
:-15
:II
:connection set: JZ-06/1, installation bracket: JZ-10
:-15...+80°C
:max. 95% r.h., non-condensing
: